Name: Modbus Remote IO Module (8DI+8DO+8AI)
Model No.: M160
The M160 Modbus
Remote I/O Module is an industrial class, isolated designed, high reliability,
high stability and high precision data acquisition module, embedded 32-Bit High
Performance Microprocessor MCU, provides a RS485 interface. It provides multi
I/O, supports standard Modbus RTU, can be intergraded into SCADA, OPC server, HMI
and other automation systems. It is design for working in the harsh industrial
application environment, widely used in a variety of industrial automation,
security monitoring system, automatically measurement and control system.
The M160 Modbus Remote
I/O module provides 8 optical-isolated digital inputs,DI1 supports max. 10MHz
high speed pulse counter, 8 isolated 12bits analog inputs, supports
0~5V,0~10V,4~20mA,0~20mA analog signal, 8 digital outputs, DO1 supports
10Hz~300KHz PWM high speed pulse output, or relay outputs. All of the I/O with
high sampling frequency and special filtering strategy to ensure it’s reliable.
The M160 Modbus Remote
I/O module can work at wide working voltage range, the range is 12 ~ 36VDC
with anti-reverse protection design. Also, it provides 1channel 12~36VDC power
output for external device to save wiring cost.
M Series Modbus Remote I/O Module Table
|
Model
|
Descriptions
|
DC
Output
|
DC
Input
|
Link
|
M100
|
1 RS485, 2 DI, 2 AI, 2 DO(Sink) or Relay
|
1 DC
|
12~36VDC
|
Details
|
M110
|
1 RS485, 4 DI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M120
|
1 RS485, 4 DI, 4 AI, 2AO, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M130
|
1 RS485, 8 DI, 4 DO(Sink) or Relay
|
1 DC
|
12~36VDC
|
Details
|
M140
|
1 RS485, 8 DI, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M150
|
1 RS485, 8 DI, 4 AI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M160
|
1 RS485, 8 DI, 8 AI, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M200
|
1 RS485, 2AO
|
1 DC
|
12~36VDC
|
Details
|
M210
|
1 RS485, 4 DI
|
1 DC
|
Details
|
M220
|
1 RS485, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M230
|
1 RS485, 4 AI
|
1 DC
|
Details
|
M240
|
1 RS485, 4 RTD, 2/3 wire PT100/pt1000
|
---
|
Details
|
M310
|
1 RS485, 8 DI
|
1 DC
|
12~36VDC
|
Details
|
M320
|
1 RS485, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M330
|
1 RS485, 8 AI
|
1 DC
|
Details
|
M340
|
1 RS485, 8 RTD, 2/3 wire PT100/pt1000
|
、
|
12~36VDC
|
Details
|
M410
|
1 RS485, 16 DI
|
1 DC
|
Details
|
M420
|
1 RS485, 16 DO(Sink) or Relay
|
、
|
Details
|
|
|
|
u Embedded 32-Bit High Performance Microprocessor MCU, inbuilt watchdog; u Power supply 12~36VDC with over voltage and phase-reversal protection; u 8 optical isolated digital input supports max. 10Mhz high speed pulse counter; u 8 digital output or relay output, DO1 supports 10Hz~300KHz high speed pulse output; uDO1 supports PWM output; u 8 isolated analog input, 12-bit resolution, supports 0~20mA,4~20mA,0-5VDC, 0-10VDC; u High sampling frequency and special filtering strategy to ensure reliability; u 1 RS485 Serial port, supports Modbus RTU Protocol; u Provides 1 channel 12~36VDC power source output for external device, saving wiring cost; u LED instructions work status, with reset button to reset, easy on-site installation and commissioning; u Using metal shell, protection class IP30. Metal shell and system security isolation, especially suitable for industrial applications in the field; u Small size, L105 * W88 * H30mm, compatible wall installation and DIN35mm industrial rail installation. |
|
|
M160
Specifications
Modbus RTU Remote I/O Module Specifications
|
• Digital
Input
|
Sensor Type
|
Wet Contact (NPN or
PNP), Dry Contact
|
I/O Mode
|
DI or Event Counter
|
Dry Contact
|
• On: short to GND=1
• Off: open=0
|
Wet Contact (DI to COM)
|
• On: 10 to 30 VDC =1
• Off: 0 to 3 VDC=0
|
Counter Frequency
|
High Speed: 10MHz(Only
the 1st Channel can be used as high speed pulse counter), Low Speed:
10KHz.
|
Digital sampling
frequency
|
500Hz
|
Digital filtering
strategy
|
Continues 3 times
|
Isolation
|
Optical Isolated,3k
VDC or 2k Vrms
|
• Digital
Output
|
Type
|
Sink or Relay
|
I/O Mode
|
DO or Relay or Pulse
Output
|
Pulse Output Frequency
|
10Hz~300KHz(Only the 1st Channel can be used as PWM high speed pulse outputs)
|
Over-Voltage Protection
|
50 VDC
|
Over-Temperature
Shutdown
|
175°C (typical), 150°C
(min.)
|
Load Current
|
Max. 500 mA per channel
|
Digital sampling
frequency
|
500Hz
|
Isolation
|
If DO is Sink type,
then no isolation. If it is Relay, then is electrical isolation.
|
• Analog
Input
|
Type
|
Differential input
|
Resolution
|
12 bits
|
I/O Mode
|
Voltage / Current
(jumper selectable)
|
Input Range
|
0 to 10 VDC, 0 to 5VDC,
0 to 20 mA, 4 to 20 mA
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
|
Sampling frequency
|
20Hz
|
Isolation
|
Electrical isolation
|
• Working
Power Requirements
|
Input Voltage
|
12 to 36 VDC, Peak
Voltage:+40VDC, Power consumption: Less than 3W;
|
Input Current
|
139 mA @ 24 VDC
|
• Power
Output
|
Output Voltage
|
12 to 36 VDC
|
Output Current
|
139 mA @ 24 VDC
|
• Serial
Port
|
RS485
|
MODBUS TU Protocol
|
Protection
|
15KV ESD Protection
|
Modbus Slave address
|
1~247
|
Baud Rate
|
1200,2400,4800,9600,19200,38400,57600,115200,128000Bps;
|
• Physical
Characteristics
|
Wiring
|
I/O cable max. 14 AWG
|
Dimensions
|
105 x 88 x 30 mm
|
Weight
|
Under 205 g
|
Mounting
|
DIN rail or wall
|
•
Environmental Limits
|
Operating Temperature
|
Standard Models: -10
to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to
185°F)
|
Ambient Relative
Humidity
|
5 to 95%
(non-condensing)
|
Altitude
|
Up to 3000 m
|
|
|
|
User Manual Download Solution Download
|
|
|
Standard Package 1xRemote I/O Module 1xUser Manual |
|
|