The M120d DeviceNet
Remote I/O Module is an industrial class, isolated designed, high reliability,
high stability and high precision data acquisition module, embedded 32-Bit High
Performance Microprocessor MCU, provides a CANBus interface. It provides multi
I/O, supports standard DeviceNet Protocol, can be intergraded into SCADA, OPC
server, HMI and other automation systems. It is design for working in the harsh
industrial application environment, widely used in a variety of industrial
automation, security monitoring system, automatically measurement and control
system.
The M120d DeviceNet
Remote I/O Module provides 4 optical-isolated digital inputs,DI1 supports max. 1MHz
high speed pulse counter, 4 isolated 12bits analog inputs, supports
0~5V,0~10V,4~20mA,0~20mA analog signal, 4 digital outputs, DO1 supports
10Hz~300KHz PWM high speed pulse output, or relay outputs, 2 channel 12bits
analog outputs, supports 0~10VDC signal output. All of the I/O with high sampling
frequency and special filtering strategy to ensure its reliable.
The M120d DeviceNet
Remote I/O Module can work at wide working voltage range, the range is 24
~ 36VDC with anti-reverse protection design. Also, it provides 1channel
24~36VDC power output for external device to save wiring cost.
MxxxC CANOpen, Mxxxd DeviceNet Series Remote I/O Module Table
|
DeviceNet
|
CANOpen
|
Descriptions
|
DC
Output
|
Link
|
M100d
|
M100c
|
1 CANBus, 2 DI, 2 AI, 2 DO(Sink) or Relay
|
1 DC
|
Details
|
M110d
|
M110c
|
1 CANBus, 4 DI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M120d
|
M120c
|
1 CANBus, 4 DI, 4 AI, 2AO, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M130d
|
M130c
|
1 CANBus, 8 DI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M140d
|
M140c
|
1 CANBus, 8 DI, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M150d
|
M150c
|
1 CANBus, 8 DI, 4 AI, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M160d
|
M160c
|
1 CANBus, 8 DI, 8 AI, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M200d
|
M200c
|
1 CANBus, 2AO
|
1 DC
|
Details
|
M210d
|
M210c
|
1 CANBus, 4 DI
|
1 DC
|
Details
|
M220d
|
M220c
|
1 CANBus, 4 DO(Sink) or Relay
|
1 DC
|
Details
|
M230d
|
M230c
|
1 CANBus, 4 AI
|
1 DC
|
Details
|
M240d
|
M240c
|
1 CANBus, 4 RTD, 2/3 wire PT100/pt1000
|
---
|
Details
|
M310d
|
M310c
|
1 CANBus, 8 DI
|
1 DC
|
Details
|
M320d
|
M320c
|
1 CANBus, 8 DO(Sink) or Relay
|
1 DC
|
Details
|
M330d
|
M330c
|
1 CANBus, 8 AI
|
1 DC
|
Details
|
M340d
|
M340c
|
1 CANBus, 8 RTD, 2/3 wire PT100/pt1000
|
---
|
Details
|
M410d
|
M410c
|
1 CANBus, 16 DI
|
1 DC
|
Details
|
M420d
|
M420c
|
1 CANBus, 16 DO(Sink) or Relay
|
---
|
Details
|
Notices
|
1.
If the
model provides digital input, the DIN default type: wet contact, optional:
dry contact. The input type cannot be changed after manufacturer delivered.
The DIN1 default is high-speed count mode, the counter frequency Max. is
1Mhz; it can be changed , , to low-speed count mode by open the shell and change
the internal jumper. If require dry contact input, please note when ordering,
if DIN1 require high-speed pulse count mode then must be wet contact.
2.
If the
model provides digital output, the DO default type: SINK, pulse output
frequency is 10Hz~300Khz. optional: Relay. The output type cannot be changed
after manufacturer delivered. The DO1 supports PWM high-speed pulse output,
the output duty cycle from 10-90%; DO2 can be used to control the direction
of the stepper motor. If require relay output, please note when ordering, if
DO1, DO2 used for high-speed pulse output then must be Sink.
3.
The
model number: M240d/c, M340d/c support thermal resistance temperature
transmitter default type: PT100, optional: PT1000, if you need PT1000 type of
thermal resistance, please note when ordering.
4.
The
valid number of I / O ports corresponding to the model number is described in
the Model List, the not included I/O port in the model label is invalid,
although in the hardware reserved them.
|
|
|
|
Features:
u Embedded 32-Bit High
Performance Microprocessor MCU, inbuilt watchdog;
u Wide range power
supply 24 ~ 36VDC with over voltage and phase-reversal protection;
u 1 CANBUS Interface, comply
with DeviceNet specification Volume I, Release 2.0 & Volume II, Release 2.0, Errata 5;
u Group 2 Only Server (non UCMM-capable) ;
u Support Predefined Master/Slave Connection Set;
u Support DeviceNet heartbeat and shutdown
messages;
u Provide EDS file for
standard DeviceNet master interface;
u 4 optical isolated digital
input, supports max. 1MHz high speed pulse counter;
u 4 digital output or relay
output, supports 10Hz~300KHz high speed pulse output;
uDO1 support PWM
output;
u 4 isolated analog input,
12-bit resolution, supports 0~20mA, 4~20mA, 0-5VDC, 0-10VDC;
u 2 analog output, 12-bit
resolution, supports 0-10VDC;
u High sampling frequency and
special filtering strategy to ensure reliability;
u Provides 1 channel 24~36VDC
power source output for external device, saving wiring cost;
u LED instructions work
status, with reset button to reset, easy on-site installation and
commissioning;
u Using metal shell,
protection class IP30. Metal shell and system security isolation, especially
suitable for industrial applications in the field;
u Small size, L105 * W88 *
H30mm, compatible wall installation and DIN35mm industrial rail installation.
|
|
|
DeviceNet Protocol Remote I/O Module
Specifications
|
• Digital
Input
|
Sensor Type
|
Wet Contact (NPN or
PNP), Dry Contact
|
I/O Mode
|
DI or Event Counter
|
Dry Contact
|
• On: short to GND=1
• Off: open=0
|
Wet Contact (DI to COM)
|
• On: 10 to 30 VDC =1
• Off: 0 to 3 VDC=0
|
Counter Frequency
|
High Speed: 1MHz(Only
the 1st Channel can be used as high speed pulse counter), Low Speed:
10KHz.
|
Digital sampling
frequency
|
500Hz
|
Digital filtering
strategy
|
Continues 3 times
|
Isolation
|
Optical Isolated,3k
VDC or 2k Vrms
|
• Digital
Output
|
Type
|
Sink or Relay
|
I/O Mode
|
DO or Relay or Pulse
Output
|
Pulse Output Frequency
|
10Hz~300KHz(Only the 1st Channel can be used as PWM high speed pulse outputs)
|
Over-Voltage Protection
|
50 VDC
|
Over-Temperature
Shutdown
|
175°C (typical), 150°C
(min.)
|
Load Current
|
Max. 500 mA per
channel
|
Digital sampling
frequency
|
500Hz
|
Isolation
|
If DO is Sink type,
then no isolation. If it is Relay, then is electrical isolation.
|
• Analog
Input
|
Type
|
Differential input
|
Resolution
|
12 bits
|
I/O Mode
|
Voltage / Current
(jumper selectable)
|
Input Range
|
0 to 10 VDC, 0 to 5VDC,
0 to 20 mA, 4 to 20 mA
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
|
Sampling frequency
|
20Hz
|
Isolation
|
Electrical isolation
|
• Analog
Output
|
Type
|
Differential input
|
Resolution
|
12 bits
|
Output Range
|
0 to 10 VDC
|
Drive Current
|
1A (max.)
|
Accuracy
|
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
|
Isolation
|
No
|
• Working
Power Requirements
|
Input Voltage
|
24 to 36 VDC, Peak
Voltage:+40VDC, Power consumption: Less than 3W;
|
Input Current
|
139 mA @ 24 VDC
|
• Power
Output
|
Output Voltage
|
24 to 36 VDC
|
Output Current
|
139 mA @ 24 VDC
|
• CANBUS
|
CANBUS Interface
|
5.08mm Terminal,
|
Protection
|
ESD 500VDC
|
Wires Connection
|
Shield Twisted wires, CAN
V+, CAN_H, CAN_L, CAN_Shield, GND
|
DeviceNet Protocol
|
Volume I, Release 2.0
&Volume II, Release 2.0, Errata 5
|
MAC ID
|
Range:0 ~ 63.
|
Baud Rate Setting
|
Range:125, 250, 500kbps
|
Predefined Master/Slave
Connection Set Rate
|
Group 2 Only Server
|
I/O Operation Mode
|
Polling
|
• Physical
Characteristics
|
Wiring
|
I/O cable max. 14 AWG
|
Dimensions
|
105 x 88 x 30 mm
|
Weight
|
Under 205 g
|
Mounting
|
DIN rail or wall
|
•
Environmental Limits
|
Operating Temperature
|
Standard Models: -10
to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to
185°F)
|
Ambient Relative
Humidity
|
5 to 95%
(non-condensing)
|
Altitude
|
Up to 3000 m
|
|
|
|
User Manual Download Solution Download
|
|
|
Standard Package 1xRemote I/O Module 1xUser Manual |
|
|